The difference between "IIC and IIB" of Shandong explosion-proof air conditioner
1, explosion-proof air conditioning installation site
1.1 The air conditioner can work normally under the following environmental conditions:
a. Atmospheric pressure 80 ~ 110KPa;
b. Ambient temperature: when cooling, indoor 17 ° C ~ 32 ° C, outdoor 18 ° C ~ 40 ° C, when heating, indoor not higher than 30 ° C, outdoor -7 ° C ~ +24 ° C;
c. Relative humidity of air: in the wettest month, the monthly average maximum relative humidity is not more than 90%; and the monthly average minimum temperature is not higher than +25 °C;
d. There is a hazardous gas mixture formed by combustible gas, steam and air in Groups IIA and IIB T1~T4, Zone 1 or Zone 2 hazardous sites;
e. Where there is no severe vibration and impact;
f. In a clean environment free from dust and water.
1.2 The air conditioner should be properly installed by qualified installation technicians according to the installation instructions in this manual.
1.3 Check the power supply voltage before installation and whether the environmental conditions are consistent with the requirements on the nameplate.
1.4 The installation location of the air conditioner should avoid the influence of bad environment such as oil smoke, heat radiation and humidity.
1.5 The installation location of the outdoor unit should avoid the direct infiltration of moisture, sea water, wind, rain, sun exposure, etc., and take precautionary measures if necessary.
2 Explosion-proof air conditioning circuit installation requirements and electrical principles
2.1 The air conditioner adopts copper core cable or steel pipe wiring, which should be installed and installed by the seller or qualified electrician.
2.2 The internal and external grounding terminals provided by the air conditioner should be reliably grounded.
2.3 If the power switch of the air conditioner is installed in the same environment, the corresponding explosion-proof products should be used.
2.4 Before using the air conditioner, it is necessary to turn on the power for at least 12 hours, and always turn on the power unless the air conditioner is not used for a long time.
2.5 Air conditioners are installed and wired according to the national standard GB3836.15.
3 Explosion-proof air conditioners must be inspected as follows before installation. If they do not meet the requirements, they are not allowed to be put into use.
3.1 There are explosion-proof signs and explosion-proof certificate number, and are consistent with the requirements of the air conditioner.
3.2 The components of the air-conditioner flameproof enclosure are correctly connected and securely fastened.
3.3 All explosion-proof parts of air conditioners should be free of cracks and defects affecting explosion-proof performance
3.4 Air conditioner should be grounded inside and outside reliably
4 Safety instructions for use of explosion-proof air conditioners
4.1 Please read this manual carefully before using this air conditioner. If you have any questions, please ask the seller for assistance.
4.2 Do not use the power switch to directly start or turn off the air conditioner. After connecting the power supply, use the opening key of the air conditioner to open and close the air conditioner.
4.3 Do not put things in the air inlet and outlet of the air conditioner, which is very dangerous.
4.4 Do not open the door or cover of the enclosure with electricity. Switch off the power switch before turning on inspection or maintenance.
4.5 The minimum outer diameter of the cable that introduces the explosion-proof electrical control box is Φ10, and it must be sealed with a sealing ring at the inlet, and the sealing ring of each cable introduction device should be replaced when it is deteriorated. The sealing ring material is XH-21, its Shore hardness is 45-55, and it is qualified according to the requirements of GB3836.1. When installing, be sure to press the sealing ring with a compression nut to ensure reliable sealing of the inlet device.
5 Explosion-proof air conditioning parts name
The air conditioner is composed of an indoor unit and an outdoor unit, and the indoor unit is an explosion-proof product. The outdoor unit is mainly composed of an explosion-proof electrical control box, a compressor, a heat exchanger, a four-way solenoid valve, a pressure switch and a fan (with a flameproof type motor). The indoor unit is mainly composed of an explosion-proof electrical control box, a fan (with an explosion-proof type motor), an intrinsically safe control panel, and an explosion-proof electrical control box.
Explosion-proof air conditioning features
1, explosion-proof air conditioning according to the structure or divided into: window air conditioner, split wall-mounted air conditioner and split cabinet air conditioner; according to the function is divided into: single cold type and cold and warm type.
2. Under normal circumstances, in order to improve the safety performance of the product and the reliability of the user's on-site operation, all explosion-proof air conditioners are designed for manual control, and can be designed as remote control according to user requirements when needed. Explosion-proof air-conditioning equipment is mainly based on domestic and foreign brand machines, using special process methods and manufacturing methods for explosion-proof treatment to ensure that air conditioners meet explosion-proof requirements.
3. Explosion-proof treatment can be carried out on special air-conditioning equipment at the user's site, such as: large-scale chillers, refrigeration units, central air-conditioning equipment, dehumidification units, and air-conditioning equipment of special installation type. We will formulate specific treatments for such explosion-proof products. The manufacturing program is submitted for user review. When necessary, we will apply for an explosion-proof testing center to conduct product explosion-proof performance testing at the customer site.
4. All explosion-proof air conditioners are shipped with a full set of product technical data and installation instructions. Please strictly install and use the instructions according to the instructions.
5. Under normal circumstances, all explosion-proof air conditioners are equipped with explosion-proof junction box for power supply and indoor and outdoor power supply connection, explosion-proof junction box and connection tube and installation accessories for signal connection, but not with explosion-proof power switch.
Explosion-proof air-conditioning products must comply with relevant national explosion-proof standards before they are allowed to enter the market.
GB3836.1-2000 Electrical equipment for explosive atmospheres - Part 1: General requirements
GB3836.2-2000 Electrical equipment for explosive atmospheres - Part 2: Explosion-proof type "d"
GB3836.4-2000 Electrical equipment for explosive atmospheres - Part 2: Intrinsically safe "ib"
GB3836.9-2006 Electrical equipment for explosive atmospheres - Part 9:
GB3836.15-2000 Electrical equipment for explosive atmospheres - Part 15: Electrical installations
JB/10538-2005 "Explosion-proof dehumidifier and air conditioner"
Choicy is professional esthetics equipment manufacturer producing IPL, SHR and DPL machine, and professional producing and selling IPL handpiece, IPL glasses, SHR treatment head, OPT treatment handle, cooling gel, and the skincare products for aftercare. To view the full range of laser machines that we have available, you are welcome to contact us to have a video online meeting to see the machines up close and personal. Also, please send your requirements with a detailed list including the style/item and quantity you require. We will then send our best prices to you. Manufacturers Machine Operation training is included with all machines and no previous experience is required.